Van-Packer GRZ Series (with Stainless Steel Inner Liner) Pre-fabricated Grease Duct System Company: Van-Packer Company

PRODUCT DESCRIPTION

Van-Packer’s Model GRZ Series (with Stainless Steel Inner Liner) Pre-fabricated Grease Duct System consists of rectangular factory-built, prefabricated, duct sections and system components that are mechanically coupled together and designed for zero clearance to combustibles except as noted in the corresponding Intertek Listing. The inside dimensions of the Model GRZ Series Grease Duct varies between 4 to 48 inches. The Model GZ Series Grease Duct is a double wall construction with the outer diameter of the outer shell being 6 to 8 inches greater than the inside diameter of the inner liner. The annular space between the inner liner and the outer shell has nominally 3 inches of alkaline earth silicate fiber insulation wrapped around the inner liner.  The Model GRZ Series (with stainless steel inner liner) ducts comply with the following specifications:
 
  1. Grease Duct Size:
  • Maximum Interior Cross-Section Area: 1296 in2
  • Maximum Interior Dimension: 48 in.
  • Minimum Interior Dimension: 4 in.
  • Maximum Interior Width to Height Ratio: 6:1
 
  1. Inner Liner: Minimum 20 GA stainless steel
 
  1. Outer Shell: Minimum 24 GA aluminized steel, galvanized steel, or stainless steel for ducts with outside dimensions less than or equal to 36 in. and minimum 20 GA aluminized steel, galvanized steel, or stainless steel for ducts with outside dimensions greater than 36 in.
 
RATINGS 
 
Standard Rating Design Number
UL 1978 Pass  VPC/FMF 120-03
UL 2221 Condition A - Pass VPC/FMF 120-03
ASTM E814 F-Rating - 2 hours
T-Rating - 2 hours
VPC/FMF 120-03
CAN/ULC-S662 Pass VPC/FMF 120-04
CAN/ULC-S144 2 hours VPC/FMF 120-04
CAN/ULC-S115 F-Rating - 2 hours
FT-Rating - 2 hours
FH-Rating - 2 hours
FTH-Rating - 2 hours
VPC/FMF 120-04
 
 
Listing Report Return to Search
Attributes
CriteriaUL 2221 (2010)
CriteriaUL 1978 (2010)
CriteriaCAN / ULC S662 (2009)
CriteriaCAN / ULC S115 (2011)
CriteriaASTM E814 (2011a)
CriteriaCAN / ULC S144 (2012)
CriteriaASTM E814 (2013a)
CriteriaUL 1978 (2013)
CSI Code23 00 00 Heating, Ventilating, and Air Conditioning (HVAC)
CSI Code05 58 00 Formed Metal Fabrications
CSI Code23 35 00 Special Exhaust Systems
CSI Code23 35 33 Listed Kitchen Ventilation Exhaust System
Listing SectionFIRE RESISTANT DUCT
Spec ID39882
Design Documents
Public Documents