McKeon FireFighter® D200 and D200E 1 Hour Fire & Smoke Barrier (with or without Hook & Loop Passage Door) Company: McKEON Code Compliance Research Reports: CCRR-0455

McKEON FireFighter® Model D200 and D200E curtain assemblies utilizing 1-hour-rated fabric are for use as a fire and smoke barrier when installed in a 1-hour steel stud/gypsum or masonry wall. Model D200E assemblies contain a passage door sealed with a hook & loop fastener. See below for ratings and limitations.

FIRE RATINGS
Test Standard Rating
UL 10D 60 minutes
UL 10B, UL 10C, NFPA 252 20 minutes without hose stream

AIR LEAKAGE RATINGS
Test Standard Test Type Ratinga
UL 1784 Ambient Temperature ≤3.0 cfm/ft2 at up to 0.10 in. of w.c.
UL 1784 Elevated Temperature ≤3.0 cfm/ft2 at up to 0.10 in. of w.c.
aThis assembly was evaluated without the use of an artificial bottom seal, and may be installed in areas where pressurization is provided to control smoke movement in accordance with Section 4.3.2 of NFPA 105 (2019) and for hoistway opening protection and lobby doorways as allowed in Chapter 30 of the IBC.

CODE COMPLIANCE RESEARCH REPORT
Evaluation Method Building Code CCRR Number
UL 10B
UL 10C
UL 10D
UL 1784
2024, 2021, 2018 IBC
2024, 2021, 2018 IFC
2023, 2020 FBC
2022 CBC
2023 LABC
2024, 2021, 2018 NFPA 101
CCRR-0455

MAXIMUM SIZE LIMITATIONS
Certification Procedure Maximum Area Maximum Width Maximum Height
LABEL 143 sq ft 13’-0” 11’-0”
CERTIFICATE/LABEL  unlimited* unlimited* unlimited*
 *Assemblies exceeding these dimensions must have an oversized label, issued by Intertek, stating the assembly is constructed in accordance with the certified design except for size. Acceptance of the oversize assembly is at the discretion of the Authority Having Jurisdiction.

MINIMUM SIZE LIMITATIONS (UL 1784 ONLY)*
Width Height
29.5" 78"
*Fire-only assemblies do not have a minimum size.
 
Minimum Bottom Bar weight: 0.30 lbs per sq. ft. of curtain area

Maximum Curtain Rivet spacing: 15” on-center
Maximum Hook & Loop length: 8’0”
Stainless Steel hook & loop required for fire applications
Side Guide anchorage: 1/4" anchors spaced maximum 18” on-center
Top Hood/Assembly mounting: maximum 40” on-center
Listing Report Certificate of Compliance Return to Search
Attributes
Certificate Date of ExpiryDecember 31, 2025
Certificate Date of Initial RegistrationApril 1, 2017
Certificate NumberWHI17 – 20384311
CriteriaUL 10(b) (2008)
CriteriaUL 1784 (2015)
CriteriaUL 10(c) (2016)
CriteriaUL 10(d) (2017) Ed.2
CSI Code08 30 00 Specialty Doors and Frames
Fire Resistance20 Min w/out Hose Positive Pressure
Fire Resistance60 Min Positive Pressure
Listing SectionSMOKE CONTROL DOOR ASSEMBLIES