McKEON SafeSpace™ SS500 and SS500F Series Tornado & Hurricane Resistant Doors Company: McKEON Code Compliance Research Reports: CCRR-0500

McKEON SafeSpace™ SS500 and SS500F Series Tornado & Hurricane Resistant Doors
The SafeSpace SS500 is certified for wind pressure and impact resistance only. The SafeSpace SS500F is certified for wind pressure, impact, and fire resistance. When fire resistance is required by Section 603 of ICC 500-2020 or Section B6.2.3 of FEMA P-361 (2021), the SafeSpace SS500F must be used.

ICC 500 WIND PRESSURE AND IMPACT RATINGS (SS500 and SS500F)
Assembly Type Permitted Size* Design Wind Pressure Impact Rating
Rolling Door Assembly
(Installed on protected
side of shelter envelope)
Min:
 4'-4" wide
 4'-0" high
Max:
 16'-4" wide
 22'-0" high
Tornado: ±252 PSF

Hurricane: ±201 PSF
15 lbs.
@
100 MPH
*Width is tip to tip of support guide angles. Permitted sizes above pertain only to ICC 500 ratings, see below for size limitations of fire-resistance-rated SS500F assemblies.

FIRE RATINGS (SS500F Only)
Test Standard Rating
UL 10B, NFPA 252, CAN/ULC S104 4 hours

AIR LEAKAGE RATINGS (SS500F Only)
Test Standard Test Type Ratinga
UL 1784 Ambient Temperature ≤3.0 cfm/ft2 at up to 0.10 in. of w.c.
UL 1784 Elevated Temperature ≤3.0 cfm/ft2 at up to 0.10 in. of w.c.
aThis assembly was evaluated without the use of an artificial bottom seal. When installed with the manufacturer-provided brushes and neoprene bottom seal, it may be installed in areas where pressurization is provided to control smoke movement in accordance with Section 4.3.2 of NFPA 105. For installations where pressurization is not used to control smoke movement, a seal at the bottom edge of the assembly is optional.

CODE COMPLIANCE RESEARCH REPORT
Evaluation Method Building Code CCRR Number
ICC 500
UL 10B
2024, 2021 IBC
2023, 2020 FBC
2022 CBC
2023 LABC
CCRR-0500               

SIZE LIMITATIONS (SS500F Only)
Certification Procedure Maximum Area Maximum Width Maximum Height
LABEL 156 sq ft 13'-0" 12'-0"
CERTIFICATE/LABEL* 294 sq ft 16'-4" 22'-0"
*The AHJ may approve "oversize" doors based on an oversized certificate/label that states the door supplied is constructed in accordance with the certified design except for the size. ICC 500 Size restrictions located in the table above still apply.

INSTALLATION LIMITATIONS
When mounted to steel supporting structure, Mounting Angles are anchored with minimum  5/8" diameter A325 bolts spaced maximum 16 inches on-center. Structural adequacy of steel supporting structure is to be determined by others and is not evaluated as part of this Listing.

When mounted to concrete supporting structure, Mounting Angles are anchored with 5/8" diameter Simpson Strong-Bolt 2 wedge anchors spaced maximum 16 inches on-center.  The tested condition utilized 4000-psi strength concrete, an embedment length of 5-1/8 inches, and an edge distance to the opening of 7-1/2 inches. Adequacy of concrete supporting structure is to be determined by others and is not evaluated as part of this Listing.

Alternate anchoring to supporting structure that maintains the maximum spacing of 16 inches on-center is to be designed by a registered design professional for pull-out, shear, and placement to resist the design loads in accordance with ICC 500-2014 Section 301 and ICC 500-2020 Section 304.

Installation shall follow these listing procedures and the manufacturer's instructions provided with each assembly. In the event of a conflict, these listing procedures govern.
Listing Report Certificate of Compliance Return to Search
Attributes
Certificate Date of ExpiryDecember 31, 2025
Certificate Date of Initial RegistrationApril 23, 2020
Certificate NumberWHI20-20384307
CriteriaICC 500 (2014)
CriteriaCAN / ULC S104 (2015) (R2020)
CriteriaUL 10(b) (2008) (R2020)
CriteriaICC 500 (2020)
CriteriaFEMA P-361 (2021) Ed.4
CriteriaNFPA 252 (2022)
CSI Code08 34 00 Special Function Doors
Listing SectionWIND LOAD RESISTANT DOORS
Spec ID43799
Windload/StructuralStorm Shelter
Windload/StructuralTornado Resistance