PRODUCTS COVERED
Firestop Systems and Components:
	
		
			| Product ID | Description | 
		
			| GrabberGard IFC | FSI Intumescent Caulk | 
		
			| GrabberGard EFC | Endothermic Caulk | 
		
			| GrabberGard EFS | Spray Mastic | 
	
 
RATINGS
Horizontal Penetrations:
	
		
			| Standards* | Rating | Design No. | 
		
			| ULC S115, ASTM E814,
 UL 1479
 | 1 Hour | JWA/PH 60-01; JWA/PH 60-02; JWA/PH 60-03; JWA/PH 60-06; JWA/PH 60-08; JWA/PH 60-09;
 JWA/PH 60-10
 | 
		
			| 2 Hour | JWA/PH 120-01; JWA/PH 120-02; JWA/PH 120-04; JWA/PH 120-05;
 JWA/PH 120-06
 | 
		
			| 3 Hour | JWA/PH 180-01 | 
	
* Refer to individual Design Listings for actual test Standards
 
Horizontal/Vertical Penetrations:
	
		
			| Standards* | Rating | Design No. | 
		
			| ULC S115, ASTM E814,
 UL 1479
 | 2 Hour | JWA/PHV 120-04; JWA/PHV 120-06; JWA/PHV 120-14; JWA/PHV 120-15;
 JWA/PHV 120-16; JWA/PHV 120-17;
 JWA/PHV 120-18; JWA/PHV 120-19
 | 
	
* Refer to individual Design Listings for actual test Standards
Vertical Penetrations:
	
		
			| Standards* | Rating | Design No. | 
		
			| ULC S115, ASTM E814,
 UL 1479
 | 1 Hour | JWA/PV 60-02; JWA/PV 60-03; JWA/PV 60-04
 | 
		
			| 2 Hour | JWA/PV 120-02; JWA/PV 120-05; JWA/PV 120-06; JWA/PV 120-07;
 JWA/PV 120-08
 | 
		
			| 4 Hour | JWA/PV 240-02 | 
		
			| ASTM E119, UL 263,
 CAN/ULC S101
 | 1 Hour | JWA/PV 60-05 | 
		
			| ASTM E814, UL 2079,
 CAN/ULC S115
 | 2 Hour | JWA/PV 120-09 | 
		
			| 4 Hour | JWA/PV 240-01 | 
	
* Refer to individual Design Listings for actual test Standards
 
EVALUATED TO THE FOLLOWING:
The listed systems in this section have been evaluated to the following requirements:
ASTM-E814, Fire Tests of Through-Penetration Firestops
CAN/ULC-S115, Fire Tests of Firestop Systems
Maintenance of integrity (stay-in-place and prevent passage of flame) when subjected to the test temperatures (standard fire exposure) in:
ASTM-E119, Fire Tests of Building Construction & Materials
CAN/ULC-S101, Fire Endurance Tests of Building Construction & Materials
Test Pressure Differential - Each listing indicates a "Test Pressure Differential" which is the amount by which the pressure on the fire exposed side of the system exceeded the pressure on the unexposed side during test.
Annular Spacing - Where annular spacing is specified in these listings for through-penetration type systems it refers to the clearance between the penetration and the opening. Where a specific distance is stated and not identified as "minimum", the penetration is centered in the opening; where a distance is specified as "minimum", the maximum spacing is governed by the maximum opening size; where a range is stated, the penetration may be offset in the opening within the clearance limitations of the spacing range given.
These systems are intended for use in the types of separations for which they are qualified in the listed design. The separations themselves should be rated for the period required per ASTM-E119, CAN/ULC-S101 or equivalent.
Where only F and T ratings (ASTM-E814) are given for a system design, these correspond to FH and FTH ratings (CAN/ULC-S115) and may be read as such.
Systems are installed, unless otherwise noted, in accordance with the Manufacturer's Installation Instructions or Design Manual.
Penetrating items must be supported as required by applicable codes on both sides of the fire barrier. Listed Firestop systems that include support for the penetrating item indicate the supporting element in the listing. Such items are not evaluated for their load carrying capacity during the fire resistance test.
All listed components are identified with the ETL Certification Mark.
Manufacturers of listed components subscribe to an Intertek follow-up factory inspection and certification program.