Intertek Directory of Building Products

3M Strap-Type Through-Penetration Firestop System Company: 3M Company

 

Product: Strap-Type Through-Penetration Firestop System

 

Model:  3M FireStrap; 3M FirePlug; IPEX FirePro System I and II

 

Limitations:  Refer to the Listings Designs  

 

Evaluated to the following...

The listed systems in this section have been evaluated to the following requirements:

CAN/ULC-S115, Fire Tests of Firestop Systems
Maintenance of integrity (stay-in-place and prevent passage of flame) when subjected to the test temperatures (standard fire exposure) in:
ASTM-E119, Fire Tests of Building Construction & Materials
CAN/ULC-S101, Fire Endurance Tests of Building Construction & Materials
Test Pressure Differential - Each listing indicates a "Test Pressure Differential" which is the amount by which the pressure on the fire exposed side of the system exceeded the pressure on the unexposed side during test.
Annual Spacing - Where annual spacing is specified in these listings for through-penetration type systems it refers to the clearance between the penetration and the opening. Where a specific distance is stated and not identified as "minimum", the penetration is centered in the opening; where a distance is specified as "minimum", the maximum spacing is governed by the maximum opening size; where a range is stated, the penetration may be offset in the opening within the clearance limitations of the spacing range given.
These systems are intended for use in the types of separations for which they are qualified in the listed design. The separations themselves should be rated for the period required per ASTM-E119, CAN/ULC-S101 or equivalent.
Where only F and T ratings (ASTM-E814) are given for a system design, these correspond to FH and FTH ratings (CAN/ULC-S115) and may be read as such.
Systems are installed, unless otherwise noted, in accordance with the Manufacturer's Installation Instructions or Design Manual.


Certified Products can be identified by the Omega Point Laboratories (OPL), Warnock Hersey (WH), or ETL Certification Mark

Manufacturers of listed components subscribe to an Intertek follow-up factory inspection and certification program.

 

Listing Report Return to Search
Attributes
CriteriaASTM E814
CriteriaULC S115 (1995)
CSI Code07 80 00 Fire and Smoke Protection
Fire Resistance2 Hour Fire Rated
Listing SectionFIRESTOP SYSTEMS
Spec ID44973