Intertek Directory of Building Products

Therma Tru 20 Minute Positive Pressure Fiberglass Skin Foam Core Fire Door without Hose Stream (20PPFFCWOH) Company: Therma Tru Corporation

Fiberglass Reinforced Faced (Proprietary Core) (Simulated Panel Type or Flush) Swinging Door for installation in up to 20 minute locations (without hose stream - see table below). For use in any "Category C - Standard" frames. These doors may also be installed in frames listed in "Category C - Proprietary" in accordance with the frame manufacturer's individual listing.
Limitations
Cylindrical/Deadbolt/Latches with maximum 2-3/4" backset/Mortise Latch/Card Reader/Surface Mounted Vertical Rod Fire Exit Devices/Rim-Type Fire Exit Devices/Viewers/Protection Plates/Surface Mounted Closers/Surface or Kerf Mounted Door Bottom.
Maximum Size of Openings
Single Swing (without hose stream) 3'0" wide x 8'0"* high
*Shaker Panel Design Maximum Height: 80"

Standard and Double Egress Pairs - Not Allowed
Testing Standard

 UL-10C (Positive Pressure), NFPA 252 

All assemblies are identified by a label or marking bearing the wording, "Listed (Product)", a time interval, temperature rise (if applicable), a serial number and the WHI Certification Mark.

(Unless otherwise specified, all Fire Doors have a nominal thickness of 1-3/4".)
Listing Report Return to Search
Attributes
CriteriaNFPA 252 (2012)
CriteriaUL 10(c) (2016)
CSI Code08 10 00 Doors and Frames
CSI Code08 15 00 Plastic Doors
Fire Resistance20 Min w/out Hose Positive Pressure
Listing SectionCATEGORY B - DOORS - ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
Spec ID45432
SwingSingle Swing
Design Documents
No Results
Public Documents
No Results