Air King America Series AS and AK combination exhaust fan ceiling damper is approved for use in fire rated floor/ceiling or roof/ceiling assemblies not exceeding a 1-hr fire-resistance rating for the combustible assemblies listed below, as an alternative to sheet metal dampers. The maximum number of ceiling dampers in an assembly is based on the approved number of sheet metal dampers in the specified design.
The following AS and AK combination exhaust fan and ceiling damper models are approved:
- FRAS50
- FRAS60
- FRAS70
- FRAS84
- FRAS90
- FRAS120
- FRAK80
- FRAK90
- FRAK110
- FRAK130
- FRAKV
Series AS and AK combination exhaust fan ceiling damper is approved for installation in floor/ceiling or roof/ceiling assemblies previously rated with a hinged-door sheet metal damper installed in the ceiling and for use with the following 1-hr fire-resistance rated combustible construction floor/ceiling and roof/ceiling assembly designs:
- L501
- L502
- L503
- L506
- L507
- L508
- L512
- L513
- L514
- L515
- L516
- L517
- L519
- L522
- L521
- L523
- L528
- L530
- L533
- L537
- L545
- L546
- L550
- L562
- L563
- L570
- L574
- L579
- L581
- L583
- L585
- L586
- M503
- M530
- M538
- P522
- P531
- P538
- P545
- P552
Exhaust fans shall be ducted out of the plenum space using any UL 181 Class 0 or Class 1 duct.