Intertek Directory of Building Products

Hydra DoorCo - Model E3684/E4884 Sliding Door Operator Company: Hydra DoorCo, LLC

The Hydra DoorCo, LLC Model E3684/E4884 is an electric-powered overhead sliding door operator intended for use in detention applications requiring fire-, and/or smoke-, rated neutral pressure fire door assemblies. 
 ++The assemblies were tested under positive pressure and can be labled with the  UL10C label at the descretion of the AHJ

NOTE: To achieve a fire-, and/or smoke-, rated assembly, the operator must be paired with an appropriately rated - and separately listed - 2" thick steel sliding door that is fire rated and intended for use in detention applications.


Model E3684
  • Clear Opening Size: 3’-0” Wide x 7' 0" High
  • Listed Door Size:      3' 2-1/2" Wide x 6' 10-1/4" High
Model E4884
  • Clear Opening Size: 3’-9-1/2” Wide x 7' 0" High
  • Listed Door Size:      48" Wide x 6' 10-1/4" High

The door operator consists of a heavy-duty steel frame installed into and around a masonry wall doorway opening. An electric powered sliding track mechanism is affixed to the frame above the wall opening and a separately listed fire-, and/or smoke-, rated 2" thick steel door intended for use in detention applications is attached to the operator’s sliding mechanism utilizing a welded connection. 

With fire-rated seals installed along the door edges (leading, trailing, & top), the operator assembly described above was tested per test method UL 1784, "Standard for Air Leakage Tests of Door Assemblies." For the air leakage compliance noted below, the assembly must have the fire-rated seals installed detailed in the manufacturing section.


AIR LEAKAGE RATINGS
Test Standard Test Type Rating a,b
UL 1784 Ambient Temperature ≤3.0 cfm/ft2 at up to 0.10 in. of w.c.
UL 1784 Elevated Temperature ≤3.0 cfm/ft2 at up to 0.10 in. of w.c.

aThe Model E4884  assembliy was evaluated with an artificial bottom seal. The assembly is not to be installed in areas where pressurization is provided to control smoke movement in accordance with Section 4.3.2 of NFPA 105 (2019) or for hoistway opening protection and lobby doorways where prohibited in Chapter 30 of the 2018 IBC.

bThe Model E3684 was tested without an artificial bottom seal. The assembly may be installed in areas where pressurization is provided to control smoke movement in accordance with Section 4.3.2 of NFPA 105 (2019) and for hoistway opening protection and lobby doorways as allowed in Chapter 30 of the 2018 IBC.
Listing Report Return to Search
Attributes
CriteriaUL 1784 (2015)
CriteriaUL 10(b) (2008) (R2015)
CSI Code08 70 00 Hardware
Fire Resistance45 Min Neutral Pressure
Fire Resistance90 Min Neutral Pressure
Fire Resistance3 Hour Neutral Pressure
Fire Resistance20 Min w/Hose Stream NP
Fire Resistance60 Min Neutral Pressure
Listing SectionDOOR & FRAME HARDWARE
Listing SectionSMOKE CONTROL DOOR ASSEMBLIES
Spec ID47389
Design Documents
No Results
Public Documents
No Results