EZ Frame Fire Window Framing with SuperLite II-XL Wall Assembly Systems
Assembly Rating - Up To 120 Minutes; Non-Bearing Wall. This glazing maintains up to or less than a 250°F (121.11°C) average temperature rise for the full duration.
SuperLite II XL - 120 Minute Assembly |
With Steel Angle |
Without Steel Angle |
Maximum Allowable Clear View Area: |
4,876 sq. in |
4,876 sq. in |
Maximum Allowable Clear View Width: |
124" |
106" |
Maximum Allowable Clear View Height: |
124" |
124" |
Minimum Stop Depth: |
5/8" |
5/8" |
Minimum Nominal Thickness: |
1-1/2" |
1-1/2" |
SuperLite II XL - 90 Minute Assembly |
With Steel Angle |
Without Steel Angle |
Maximum Allowable Clear View Area: |
4,876 sq. in |
4,876 sq. in |
Maximum Allowable Clear View Width: |
124" |
124" |
Maximum Allowable Clear View Height: |
124" |
124" |
Minimum Stop Depth: |
5/8" |
5/8" |
Minimum Nominal Thickness: |
1-1/2" |
1-1/2" |
SuperLite II XL - 60 Minute Assembly |
With Steel Angle |
Without Steel Angle |
Maximum Allowable Clear View Area: |
4,952 sq. in |
4,952 sq. in |
Maximum Allowable Clear View Width: |
124" |
124" |
Maximum Allowable Clear View Height: |
124" |
124" |
Minimum Stop Depth: |
5/8" |
5/8" |
Minimum Nominal Thickness: |
1" |
1" |
SuperLite II XLM- C* - 60 Minute Assembly** |
With Steel Angle |
Maximum Allowable Clear View Area: |
3355 sq. in |
Maximum Allowable Clear View Width: |
95-1/4" |
Maximum Allowable Clear View Height: |
95-1/4" |
Minimum Stop Depth: |
5/8" (1/2" bite) |
Minimum Nominal Thickness: |
0.90" (23mm) |
* Using Safti-First SuperLite II XLM-C glazing, 23 or 27mm thick. and IG option is also allowed.
SuperLite II XL - 45 Minute Assembly |
With Steel Angle |
Without Steel Angle |
Maximum Allowable Clear View Area: |
4,952 sq. in |
4,952 sq. in |
Maximum Allowable Clear View Width: |
124" |
124" |
Maximum Allowable Clear View Height: |
124" |
124" |
Minimum Stop Depth: |
5/8" |
5/8" |
Minimum Nominal Thickness: |
3/4" |
3/4" |
Glazing Markings: W-OH-45, W-OH-60, W-OH-90, and W-OH-120
Component Bearing the Warnock Hersey Certification Mark
** SuperLite II XLM-C is only eligible for W-45 or W-60 glazing markings, it is not certified to UL 9 or NFPA 257.
Note: For applications of this glazing product in door assemblies and window assemblies as well as door vision panel kits, please see other Intertek listings in appropriate sections.
Note: Listed fire-rated glazing tape or intumescent caulk is allowed for use with SuperLite II-XL Glazing such that it is approved for fire-rated durations equal to or greater than the respective SuperLite II-XL Glazing product it is used with.
Evaluated to the following...
Unless otherwise noted, the assemblies in this section have been evaluated for conformance to the following standards:
ASTM E119, Standard Methods of Fire Tests of Building Construction and Materials.
CAN/ULC S101, Standard Methods of Fire Endurance Tests of Building Construction and Materials.
NFPA 257, Standard on Fire Test for Window and Glass Block Assemblies.
UL 263, Fire Tests of Building Construction and Materials.