Product |
Solid Fuel Room Heater |
Brand Name |
Jotul |
Description |
Materials:
Welded steel firebox with cast iron top plate, flue collar, side panels, door, ash lip, and legs.
Stainless steel baffle
Firebrick lining
Ceramic glass panel
Dimensions:
29.75-inches High x 22.25-inches Wide x 31.0-inches Deep
Air Induction:
Primary air is introduced through an inlet directly above the load door inside the firebox. Air volume is controlled manually by an external lever below the door. Primary air enters the unit through inlets at the front of the bottom plate and is channeled as air wash over the door glass and through manifold at the firebox floor level.
Flue Outlet:
6-inch diameter cast iron collar. Top or rear exit. |
Models |
F45 V2 |
Model Similarity |
None |
Ratings |
115V, 60Hz, 40W - Blower |
CLEARANCES TO COMBUSTIBLE CONSTRUCTION
CLEARANCES (UNPROTECTED WALLS) |
|
Side (in/mm) |
Back (in/mm) |
Corner (in/mm) |
Single wall connector |
15/381 |
15/406 |
11/280 |
Single wall connector w/ flue collar heat shield |
15/381 |
10/254 |
11/280 |
Double wall connector |
15/381 |
6/152 |
11/280 |
Double wall connector w/ flue collar heat shield |
15/381 |
6/152 |
11/280 |
CLEARANCES (PROTECTED WALLS) |
|
Side (in/mm) |
Back (in/mm) |
Corner (in/mm) |
Single wall connector |
5/127 |
4/102 |
3.5/89 |
Single wall connector w/ flue collar heat shield |
5/127 |
4/102 |
3.5/89 |
Double wall connector |
5/127 |
4/102 |
3.5/89 |
Double wall connector w/ flue collar heat shield |
5/127 |
4/102 |
3.5/89 |
MINIMUM ALCOVE DIMENSIONS |
|
Unprotected Walls |
Protected Walls |
Width (in/cm) |
50.25/127.6 |
34.25/87 |
Height (in/cm) |
72/183 |
65/165 |
Depth (in/cm) |
48/121.9 |
48/121.9 |
SINGLE WALL CONNECTOR (UNPROTECTED WALLS) |
Back (in/mm) |
14/356 |
Sides (in/mm) |
17/432 |
SINGLE WALL CONNECTOR (PROTECTED WALLS) |
Back (in/mm) |
6/152 |
Sides (in/mm) |
7/178 |
FLOOR PROTECTION REQUIREMENTS
Unit is acceptable for use on a combustible surface. A non-combustible protective cover must be placed a minimum of 16-inches from the front and 8-inches beyond both sides for the fueling door. Floor protection must extend 2-inches beyond each side of a horizontal chimney connector.