Jotul Model F45 V2 Solid Fuel Room Heater - Safety Company: Jøtul North America, Inc.

Product Solid Fuel Room Heater
Brand Name Jotul
Description Materials:
Welded steel firebox with cast iron top plate, flue collar, side panels, door, ash lip, and legs.
Stainless steel baffle
Firebrick lining
Ceramic glass panel
Dimensions:
29.75-inches High x 22.25-inches Wide x 31.0-inches Deep
Air Induction:
Primary air is introduced through an inlet directly above the load door inside the firebox. Air volume is controlled manually by an external lever below the door.  Primary air enters the unit through inlets at the front of the bottom plate and is channeled as air wash over the door glass and through manifold at the firebox floor level.  
Flue Outlet:
6-inch diameter cast iron collar. Top or rear exit.
Models F45 V2
Model Similarity None
Ratings 115V, 60Hz, 40W - Blower

CLEARANCES TO COMBUSTIBLE CONSTRUCTION
CLEARANCES (UNPROTECTED WALLS)
  Side (in/mm) Back (in/mm) Corner (in/mm)
Single wall connector 15/381 15/406 11/280
Single wall connector w/ flue collar heat shield 15/381 10/254 11/280
Double wall connector 15/381 6/152 11/280
Double wall connector w/ flue collar heat shield 15/381 6/152 11/280
 
CLEARANCES (PROTECTED WALLS)
  Side (in/mm) Back (in/mm) Corner (in/mm)
Single wall connector 5/127 4/102 3.5/89
Single wall connector w/ flue collar heat shield 5/127 4/102 3.5/89
Double wall connector 5/127 4/102 3.5/89
Double wall connector w/ flue collar heat shield 5/127 4/102 3.5/89
 
MINIMUM ALCOVE DIMENSIONS
  Unprotected Walls Protected Walls
Width (in/cm) 50.25/127.6 34.25/87
Height (in/cm) 72/183 65/165
Depth (in/cm) 48/121.9 48/121.9
 
SINGLE WALL CONNECTOR (UNPROTECTED WALLS)
Back (in/mm) 14/356
Sides (in/mm) 17/432
 
SINGLE WALL CONNECTOR (PROTECTED WALLS)
Back (in/mm) 6/152
Sides (in/mm) 7/178

FLOOR PROTECTION REQUIREMENTS
Unit is acceptable for use on a combustible surface. A non-combustible protective cover must be placed a minimum of 16-inches from the front and 8-inches beyond both sides for the fueling door. Floor protection must extend 2-inches beyond each side of a horizontal chimney connector.
Listing Report Return to Search
Attributes
CriteriaULC S628 (1993) (R. 2016)
CriteriaULC S627 (2000)
CriteriaUL 1482 (2011)
CSI Code10 30 00 Fireplaces and Stoves
Fuel TypeSolid Fuel - Wood
Listing SectionSOLID FUEL TYPE ROOM HEATERS