General Coatings Ultra-Thane 050, Ultra-Thane 050 MAX, Ultra-Thane 050 MAX PRO, UPC 500, UPC 500 MAX and UPC 500 MAX PRO Spray-applied Polyurethane Foam Plastic Insulation
Company: General Coatings Manufacturing Corp.
Code Compliance Research Reports: CCRR-0358
Ultra-Thane 050, Ultra-Thane 050 MAX, Ultra-Thane 050 MAX PRO, UPC 500, UPC 500 MAX and UPC 500 MAX PRO: The insulations are two-component, open cell, spray-applied polyurethane foam plastics. Ultra-Thane 050 and UPC 500 have a nominal in-place density of 0.52 pcf. Ultra-Thane 050 MAX, Ultra-Thane 050 MAX PRO, UPC 500 MAX and UPC 500 MAX PRO have a nominal in-place density of 0.45 pcf. The insulations are produced in the field by combining a polymeric isocyanate (A component) with a resin (B component).
The insulations meet the requirements of Mandatory Testing and selected Optional Testing of ICC-ES Acceptance Criteria for Spray-applied Foam Plastic Insulation (AC377) for a low-density insulation as described in Code Compliance Research Report CCRR-0358.
FLAME SPREAD RATINGS
| Test Standard |
Flame Spread Index |
Smoke Developed Index |
| ASTM E84 |
25 or less |
450 or less |
FIRE RATINGS
| Test Standard |
Configuration / Details |
Rating |
| NFPA 285 |
See GCM/FI 30-01 |
Meets requirements as configured |
| NFPA 286 |
See CCRR-0358 |
Met acceptance criteria of
IBC Section 803.1.1.1 and
IRC Section R302.9.4 as
configured |
ICC-ES AC377,
Appendix X |
See CCRR-0358 |
Met requirements as
configured |
CODE COMPLIANCE RESEARCH REPORT
| Evaluation Method |
Building Code |
CCRR Number |
| ICC-ES AC377 |
2024, 2021, 2018 IBC
2024, 2021, 2018 IRC
2024, 2021, 2018 IECC
2026, 2023 FBC (including HVHZ) |
CCRR-0358 |