Glassprotex (GPX) with INFERNOGARD ™ Wall Assembly Systems
Assembly Rating - Up To 2 Hours; Non-Bearing Wall. This glazing maintains up to or less than a 250°F (121.11°C) average temperature rise for the full duration.
INFERNOGARD ™ - 120 Minute Assembly |
Maximum Allowable Clear View Area |
4,876 sq. in |
Maximum Allowable Clear View Width |
124" |
Maximum Allowable Clear View Height |
124" |
Minimum Stop Depth |
5/8" |
INFERNOGARD ™ - 90 Minute Assembly |
Maximum Allowable Clear View Area |
4,876 sq. in |
Maximum Allowable Clear View Width |
124" |
Maximum Allowable Clear View Height |
124" |
Minimum Stop Depth |
5/8" |
INFERNOGARD ™ - 60 Minute Assembly |
Maximum Allowable Clear View Area |
4,952 sq. in |
Maximum Allowable Clear View Width |
124" |
Maximum Allowable Clear View Height |
124" |
Minimum Stop Depth |
5/8" |
INFERNOGARD ™ - 45 Minute Assembly |
Maximum Allowable Clear View Area |
4,952 sq. in |
Maximum Allowable Clear View Width |
124" |
Maximum Allowable Clear View Height |
124" |
Minimum Stop Depth |
5/8" |
Note: For applications of these glazing products in door assemblies and window assemblies as well as door vision panel kits, please see listing in appropriate sections.
Note: Listed fire-rated open cell glazing tape is allowed for use with INFERNOGARD ™ Glazing such that it is approved for fire-rated durations equal to or greater than the respective INFERNOGARD ™ Glazing product it is used with.
Note: Glazing products used in the designs specified in this Listing are non-directional.
Evaluated to the following...
Design listings are based on, and supported by, proprietary test reports. The test reports further define proprietary design details which make these listings applicable only to the specified products manufactured by the listed manufacture.
Unless otherwise noted, the assemblies in this section have been evaluated for conformance to the following standards:
ASTM-E119, Standard Methods of Fire Tests of Building Construction and Materials.
CAN/ULC-S101, Standard Methods of Fire Endurance Tests of Building Construction and Materials.
UL-263, Fire Tests of Building Construction and Materials.
Designs listed are minimum construction requirements to achieve fire rating.
Unless otherwise noted, fire ratings apply to tests conducted on both sides.