FIRE RESISTANT PRODUCTS & COMPONENTS
CATEGORY A DOORS - NO ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
PRODUCT COVERED
DeanSteel DSPROJ 3 Hour Fire Door, Hollow Metal Type (16,18, & 20 gauge faces) (Paper Honeycomb Core, or Polystyrene)
PRODUCT DESCRIPTION
Hardware Limitations: Cylindrical / Cylindrical with Deadbolt / Mortise / Card Reader / Rim-Type Surface Mounted Fire Exit Devices / Surface Mounted Door Bottoms / Surface Mounted Closers/ Viewer / 16" Protection Plates.
Temperature Rise - Greater than 650°F at 30 minutes.
Configuration |
Maximum Size |
Single Swing |
4’-0” wide by 8’-0” tall |
Standard Pairs |
8’-0” wide by 7’-2” tall |
Double Egress |
Not Allowed |
Vision Panels
Door Fire Rating |
Maximum
Visible Area
(square inches) |
Maximum
Visible Width
(inches) |
Maximum
Visible Height
(inches) |
Glazing Materials |
20 Minutes |
1296 |
54 |
54 |
Listed and labeled glazing materials |
20 Minutes |
2856 |
34 |
84 |
Pilkington ¼” thick wired glass1 or listed ceramic glazing |
20 Minutes
(Without Hose) |
2971 |
35.75 |
81.125 |
Listed and labeled glazing materials |
45 Minutes |
1296 |
54 |
54 |
Listed and labeled glazing materials |
45 Minutes |
2856 |
34 |
84 |
Pilkington ¼” thick wired glass1 or listed ceramic glazing |
60 Minutes |
100 |
33 |
33 |
Listed and labeled glazing materials |
60 Minutes |
552 2. |
18 |
36 |
Pilkington ¼” thick wired glass1 or listed ceramic glazing |
90 Minutes |
100 |
33 |
33 |
Listed and labeled glazing materials |
90 Minutes |
552 2. |
18 |
36 |
Pilkington ¼” thick wired glass1. or listed ceramic glazing |
3 Hour |
100 |
33 |
33 |
FireLite or FireLite Plus or listed 3 hr ceramic glazing |
Footnotes:
1. Listed and labeled Pilkington ¼” thick wired installed into “VL3000” (by Air Louvers Inc) or “TG4” (by Leslie-Locke Inc.) used with PEMKO’s "FG 3000 Fire Glaze" glazing compound.
2. Each door leaf can have up to four (4) vision panels, each with a maximum of 552 square inches clear view area.
The product noted above has been tested and qualified per UL 10B, UL 10C, NFPA 252, and CAN / ULC S104 for a 3 Hour Positive Pressure Fire Rating.
These doors are eligible for use in any "Category C - Standard" frame. These doors may also be installed in frames listed in "Category C - Proprietary" in the accordance with the frame manufacturer's individual listing.
The door noted above is eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.
Evaluated to the following...
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
CAN/ULC-S104, Standard Method for Fire Tests of Door Assemblies
NFPA-252, Standard Methods for Fire Tests of Door Assemblies
UL-10(b), Fire Tests of Door Assemblies
UL-10(c), Fire Tests of Swinging Door Assemblies
and are installed in accordance with the following:
NFPA-80, Fire Doors and Windows
Manufacturer's Instructions
All assemblies are identified by a label or marking bearing the wording, "Listed (Product)", a time interval, temperature rise (if applicable), a serial number and the Intertek WH Certification Mark.
Unless otherwise specified, the Fire Doors referenced above have a minimum thickness of 1-3/4".