Intertek Directory of Building Products

Dortek Inc. - Fire Door (Category A) - F Type - UL 10C Company: Dortek Inc.

Product Covered
Dortek Inc. - Fire Door (Category A) - F Type - UL 10C

Category A Doors - No additional edges-sealing system required

Product Description
Door Leaf - Glass reinforced concrete (GRC) based door leaf with GRP facings - Nominal thickness - 44 to 46mm, with 40mm thick core, for installation in listed Category C - GRP/Steel/Stainless-Steel Frames. 

Door leaf incorporates concealed intumescent strip on the top and vertical edges.

Hardware and latching requirements - UL 10C listed mortise single point center latching hardware or listed surface mounted vertical rods - (top and bottom) with panic bar. Electric retraction option is allowed with both types with provision for the cable through the exit device.

Option A:
Dortek Vision Panel Kit is allowed for up to 90-minute rating with Maximum sight size - 230mm x 230mm (w x h) and for up to 60-minute rating with Maximum sight size - 375mm x 575mm (w x h). Glass - a combination of 6mm thick tempered glass (outer glass panels) and 5mm thick Firelite glass (inner glass pane), overall thickness is 40mm or alternative listed glazing.
Option B:
Dortek Vision Panel Kit is allowed for up to 90-minute rating - Maximum sight size -150mm x 797mm (w x h) or 350mm x 547mm (w x h). Glass - Pyrobel 120, 40mm thick glazing panes installed with 3mm stainless-steel flanges.

Electric Power Transfer Unit with 10mm conduit in door from lockset to hinge edge (ref: Assa Abloy – Securitron EL-EPT/EL-EPT-SC or alternative listed hardware) is allowed.

Lead lined doors are allowed.

Fire Ratings
The product noted above has been tested and evaluated according to UL 10C - Positive Pressure Fire Tests of Door Assemblies and has qualified for the following applications and fire ratings:
Configuration Rating Maximum leaf dimension Frame type
Single leaf 1 hour (60 minutes) 1219 x 2438 (mm, w x h) GRP/Steel/Stainless Steel
1-1/2 hour (90 minutes) 1225 x 2743(mm, w x h) GRP
Double leaf 1 hour (60 minutes) 1219 x 2438 (mm, w x h) GRP/Steel/Stainless Steel
1-1/2 hour (90 minutes) 1225 x 2743(mm, w x h) GRP
Double action double leaf 1/3 hour (20 minutes) 1024 x 2040 (mm, w x h) GRP

Note - The doors are eligible to bear "S" mark (for smoke and draft control assemblies) with the use of listed Category H - Smoke & Draft Control Gasket at the head and jambs. Pairs require an additional Category H gasket applied on the meeting edge.  Please refer to gasket manufacturer's listings for installation instructions. Note – Smoke rating is only applicable to flush doors.
Listing Report Certificate of Compliance Return to Search
Attributes
Certificate Date of ExpiryDecember 31, 2026
Certificate Date of Initial RegistrationDecember 09, 2020
Certificate NumberWHI19-33626002
CriteriaUL 10(c) (2016)
CSI Code08 10 00 Doors and Frames
Fire Resistance20 Min w/Hose Stream PP Cat A Door
Fire Resistance60 Min PP Category A Door
Fire Resistance90 Min PP Category A Door
Listing SectionCATEGORY A - DOORS - NO ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
Spec ID58616
Design Documents
No Results
Public Documents
No Results