Intertek Directory of Building Products

Quietflex - Flexible Air ducts (Model: QAS Flex, QASC Flex And QAS Acoustic flex) - UL 181 Company: Quietflex Manufacturing Company, L.P.

PRODUCT COVERED
Quietflex - Flexible Air ducts (Model: QAS Flex, QASC Flex And QAS Acoustic flex) - UL 181.

PRODUCT DESCRIPTION 
This report consists of flexible air ducts and air connectors sizes 4 through 18 in. The duct consists of a wire helix reinforced core, wrapped with a fiberglass insulation which in turn is covered with a reinforced vapor barrier.

MODELS
Flexible air ducts designated as "QAS Flex", "QASC Flex",and "QAS Acoustic flex".

MODEL SIMILARITY
QAS models are the same as QASC models except that the QASC model is a 7 foot length of the QAS model with a galvanized steel collar attached to each end.

RATINGS
UL 181 Reaction to Fire Classification Class 1*

FLAME SPREAD RATINGS
Test Standard Flame Spread Smoke Development
UL723 25 or less 50 or less
*Class 1 – Air ducts and air connectors having a flame-spread index of not over 25 without evidence of continued progressive combustion and a smoke-developed index of not over 50.

LIMITATIONS
Residential:

Maximum rated positive pressure: 4 IN. WG
Maximum rated negative pressure: 1/2 IN. WG
Maximum rated velocity: 3000 FPM.

Commercial:
Maximum rated positive pressure: 4 IN. WG
Maximum rated negative pressure: 1/2 IN. WG
Maximum rated velocity: 3000 FPM

Note: A representative sample of the listed devices has been tested, investigated and found to comply with the requirements of the Standard(s) for UL 181:2013, "Standard for Factory Made Air Ducts & Connectors" and are identified with the ETL Listed Mark.
Listing Report Return to Search
Attributes
CriteriaUL 723 (2018) Ed.11
CriteriaUL 181 (2013) Ed.11 (R2021)
CSI Code23 33 00 Air Duct Accessories
Listing SectionFACTORY MADE AIR DUCTS & CONNECTORS & VAPOR BARRIERS
Spec ID58679