Intertek Directory of Building Products

Sherwin-Williams Protective & Marine Coatings - FIRETEX® FX9502 Company: Sherwin-Williams Protective & Marine Coatings - FIRE

FIRETEX® FX9502 is a high solids epoxy intumescent coating for the fire protection of steel structures.
 
FIRETEX FX9502 is a two component epoxy coating used to enhance the fire resistance of structural materials by providing a layer of insulation, which is formed as a result of a chemical reaction initiated by fire. This insulation reduces the rate of heat transfer and extends the time period for which the structural material can resist the weakening effects of the heat. It is designed to protect against the severe conditions that are associated with the combustion of cellulosic materials (wood, paper, cardboard, natural fabrics, etc.).
 
A manufacturer approved anti- corrosive primer and/or topcoat can be applied.
 
Normal in service temperature range for FIRETEX FX9502 is between -20°C (-4°F) and 80°C (176°F). Please consult Sherwin-Williams Technical Customer Support for advice regarding temperatures outside this range.
 
It is preferred that all applicators of FIRETEX FX9502 have undergone training by Sherwin-Williams prior to undertaking application work on a project.
 
Since product failure could threaten life in an emergency fire situation, applicators must not deviate from recommendations without express written agreement from an authorized Sherwin-Williams FIRETEX™ representative.
 
RATINGS
Standard Rating Design Listing
ASTM E84 Flame Spread Index – ≤ 25
Smoke Developed Index - ≤ 50
N/A
ASTM E119,
CAN-ULC-S101
Rectangular Hollow Steel Section Columns SWC/IF 180-02
ASTM E119,
CAN-ULC-S101
W-Section Columns SWC/IF 240-03
ASTM E119,
CAN-ULC-S101
Loaded Un-Restrained and Restrained Beams SWC/IF 240-04
Listing Report Certificate of Compliance Return to Search
Attributes
Certificate Date of ExpiryApril 12, 2026
Certificate Date of Initial RegistrationApril 12, 2021
Certificate NumberWHI21-28187101
Classification - Flame Spread Index<=25
Classification - Smoke Developed Index<=50
CriteriaCAN / ULC S101 (2014)
CriteriaUL 723 (2018) Ed.11
CriteriaASTM E84 (2020)
CriteriaASTM E119 (2020)
CSI Code07 80 00 Fire and Smoke Protection
CSI Code07 81 00 Applied Fireproofing
CSI Code07 81 23 Intumescent Fireproofing
Listing SectionBUILDING MATERIALS WITH SURFACE BURNING CHARACTERISTICS
Listing SectionROOF/CEILING, FLOOR/CEILING, BEAM & COLUMN ASSEMBLIES
Spec ID58754
Design Documents
Public Documents
No Results