PRODUCT DESCRIPTION
Product |
Solid Fuel Room Heater |
Brand Name |
Cleveland Iron Works, Master Forge, Enerco |
Description |
Solid fuel room heater manufactured from sheet steel with three stainless steel tubes located under the ceramic board baffle to supply secondary air. Primary air enters the firebox at the lower front of the firebox.
Baffle:
- Location: between top of combustion chamber and hearth
- Restriction: 18.250 X 2.125 inches at the front of unit
- Dimensions: covers the hearth area minus the restriction at front
- Material: Material: ½” Ceramic Board, 23lb/cu ft, 3/4” ceramic wool blanket
Firebox material:
- Firebrick 1 ¼ thick lining cover all sides and bottom
Flue gas exhaust:
- Location: Top
- Dimensions: 6 inches
- Material: Steel
Gasket:
- Door: Fiberglass rope. 9/16” dia. Low density
- Glass: Fiberglass 3mm X 16mm Flat
Overall unit dimension:
- Usable volume: 2.28 cu/ft.
- Overall heater dimension: 22.75-inch-wide 28.00-inch-deep 31.50 inch high
Convection fan:
- Manufacturer: US Stove
- Model: CB36
- CFM: 100CFM
|
Models |
Cleveland Iron Works Model: WS110
Master Forge Model: H110
Enerco Models: C110, D110, J110, N110, R110, T110, V110 |
Model Similarity |
The C110, D110, H110, J110, N110, R110, T110, and V110 models are all identical to the WS110, with no changes to the components or design. |
Ratings |
Blower – 120V, 0.26A, 60Hz |
CLEARANCES TO COMBUSTIBLE CONSTRUCTION
CLEARANCES |
Backwall to unit |
8.5-in/216 mm |
Sidewall to unit |
17-in/432 mm |
Backwall to connector |
14-in/356 mm |
Sidewall to connector |
25-in/635 mm |
Corner to unit |
6.5-in/165 mm |
FLOOR PROTECTION REQUIREMENTS
Unit is acceptable for use on a combustible surface. A non-combustible protective cover must be placed a minimum of 16-inches (18-in for Canada) from the front and 8-inches beyond both sides for the fueling door. Floor protection must extend 2-inches beyond each side of a horizontal chimney connector.