STARC 60 Minute Fire Door Frame for Use with STARC FireBlock Wall System (Spec ID 63976) Company: STARC Systems, Inc.

FIRE DOOR FRAMES
Steel Door Frame (12-16 gauge) - frame consists of 2 halves riveted together with 3/16" steel rivets.   For installation in 60 Minute proprietary wall design as noted in Intertek Spec ID 63976.  The wall utilizes a proprietary design that interlocks into the panel system through a set of interlocking tabs on both sides of the frame.  For use with listed wood or wood-composite doors or listed commercial steel doors (honeycomb, foam, temperature rise, or steel stiffened core).
 
Maximum Size of Openings: Singles - 48" wide x 80" high
Pairs -  'Not Allowed'
Double Egress - "Not Allowed"
Frame depth 6.0"
Face Width 3.0"
 
 
Frames Evaluated to the Following:
Unless otherwise noted, assemblies in this section have been tested to the following standards:

NFPA-252, Standard Methods of Fire Tests of Door Assemblies;
UL-10B, Standard for Fire Tests of Door Assemblies;
UL-10C, Standard for Positive Pressure Fire Tests of Door Assemblies;
CAN/ULC S104;
and are installed, unless otherwise noted, in accordance with the following:
NFPA-80, Standard for Fire Doors and Other Opening Protectives;
Manufacturer's Installation Instructions;
All frames are identified by  a label  bearing the wording "Fire Door Frame" and the Intertek WH Certification Mark for 60 minute fire protection.
Listing Report Return to Search
Attributes
CriteriaCAN / ULC S104 (2015) (R2020)
CriteriaUL 10(c) (2016)
CriteriaNFPA 252 (2017)
CSI Code08 10 00 Doors and Frames
Fire Resistance60 Min PP Category C Proprietary Frame
Fire Resistance20 Min w/Hose Positive Pressure
Fire Resistance45 Min Positive Pressure
Listing SectionDOOR FRAMES
Spec ID64240