The wood version Rite Door® by Adams Rite is an Integrated Door Opening Assembly consisting of architectural commercial swinging fire-rated wood door (Minimum thickness 1-3/4”) which includes fire door hardware for installation for single swing installed in labeled 14/16/18 gauge steel frames in 20/45/60/90 minute locations. Less than 450ºF temperature rise @ 30 minutes. Factory-Installed Model Nos. D3981 Series Concealed Vertical Rod (less bottom rod) with one thermal bolt from door to floor.
Limitations:
Door Construction; 20/45/60/90 Min. For use in approved listed White or Blue Mineral Core construction per the Georgia Pacific Intertek procedures. See the full contents of this listing for additional details.
Hinges per NFPA-80, and as listed by Georgia Pacific.
Vision Lite kit – Maximum 1296 sq. in. for 20/45-minute; 100 sq. in. for 60/90-minute.
Top latching only with one thermal fire pin door to floor required.
Gasketing - Listed intumescent centered on rabbets on both jambs and head of door frame or concealed within stiles and top rail of door as listed by Georgia Pacific.
For Smoke & Draft Control assemblies ("S" Label) a positive pressure listed gasket shall be used. Metal and plastic kick plates allowed per NFPA-80 up to 16" height. HPL (plastic laminate) skins may be applied to door faces. Hinge edge can be supplied with fire-rated power transfer devices.
Configuration |
Maximum Size* |
Single |
4'-0" wide x 8'-0" high (up to 90 minute) |
*See manufacturer's installation instructions for additional information, restrictions and limitations.
Testing Standards: NFPA 252, UL-10C, CAN/ULC S104 (Positive Pressure).
Evaluated to the following...
This category includes doors evaluated with an edge-sealing system 20/45/60/90 Min doors evaluated with a sealing system incorporated (concealed or visible) into the edge of the door by the licensed manufacturer or machining distributor.
These doors are eligible for use in any "Category C - Standard" frame. These doors may also be installed in frames listed in "Category C - Proprietary" in the accordance with the frame manufacturer's individual listing.
All doors listed in Category A and B are eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.
All doors in this category are identified by a label or marking bearing the wording, "Listed Fire Door", a time interval, a temperature rise rating, a serial number and the Warnock Hersey Certification Mark and "UL-10C & CAN4 S104".