ASSEMBLIES
Columbia 90 minute fire rated elevator door assemblies as noted below:
APPROVED ASSEMBLIES |
|
MAXIMUM CLEARVIEW OPENING* |
NOMINAL DOOR PANEL SIZE** |
LABEL TYPE |
TYPE |
WIDTH |
HEIGHT |
WIDTH |
DOOR/FRAME |
|
CO |
61.5 in. |
120.75 in. |
32 in. |
Standard Certification |
|
2CO |
121.5 in. |
120.75 in. |
32 in. |
Standard Certification |
|
3CO |
121.5 in. |
120.75 in. |
22 in. |
Standard Certification |
|
CO |
61.5 in. |
168 in. |
32 in. |
Oversize |
|
2CO |
121.5 in. |
168 in. |
32 in. |
Oversize |
|
3CO |
181.5 in. |
168 in. |
32 in. |
Oversize |
*Smaller sizes (w x h) are allowed.
**Door height is dependent on overall assembly size.
KEY:
CO:Center Opening (2 Door Panels)
2CO: Two Speed Center Opening (4 Door Panels)
3CO: Three Speed Center Opening (6 Door Panels)
RATINGS
Test Standard |
Assembly |
Rating |
UL10B
NFPA 252 |
Elevator Door Assemblies (See Above) |
90 Minute Neutral Pressure |
LIMITATIONS
Columbia elevator doors are limited to maximum opening sizes as shown in the table above. Each door panel has a maximum size nominally 32" wide by 122" high (standard certification label applications). [Taller doors are allowed for oversize applications as noted in the table above.] Installation must be into code compliant fire resistant rated structures (walls, sills, hardware) as contained in this listing. [For drywall wall applications a 3 hour listed wall design must be used. Installation in listed masonry walls is optional.] Door and frame assemblies are to be marked with the Warnock Hersey certification label outlining the fire protection of the elevator doors.