Elochoman Millwork 20 Minute Solid Core Wood Fire Door Procedure
CAT B - Additional edge sealing system required.
Solid Core, Swinging Flush Door for installation in 20 minute with hose stream locations. These doors require a listed intumescent edge-sealing system (Category G) applied to the perimeter of the labeled frame or door. The application of the edge-sealing system does not require any machining of the frame or door. Please refer to "Category G - Edge-Sealing System" for individual manufacturer's listings.
Limitations*
Cylindrical/Deadbolts/Surface Mounted Rim Type Fire Exit Devices/Surface Mounted Vertical Rod Fire Exit Devices/Mortise Exit Devices/Surface Mounted Closers/Viewers/Surface Mounted Plates
Configuration |
Maximum Size |
Single Swing |
4’-0” wide by 9-0” tall |
Standard Pair |
Not Allowed |
Double Egress |
Not Allowed |
*See manufacturer's installation instructions for additional information on Smoke & Draft control, size restrictions and limitations.
These doors may be installed in any listed and rated solid wood frame in accordance with the frame manufacturer's individual listing.
All doors listed in Category B are eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.
Evaluated to the following
Unless otherwise noted, the product listed above in this section has been evaluated for conformance to the following standards:
- UL 10C – Positive Pressure Fire Test of Door Assemblies
- NFPA 252 – Fire Test of Door Assemblies
- CAN/ULC S104 – Standard Method for Fire Test of Door Assemblies