Intertek Directory of Building Products

Belldinni 20 Minute Flush Wood Core Fire Doors Company: Belldinni Inc

Category A Doors – No additional edge sealing system required.
Particleboard wood core, swinging flush doors for installation in up to 20 minutes (with hose stream) locations.  These doors are eligible for use in any “Category C – Standard Frames” or in any “Category C – Proprietary Frames” in accordance with the frame manufacturer’s individual listing(s).

Limitations*
Cylindrical latches with a maximum 5” backset/Surface Mounted Vertical Rod Exit Devices/Rim Exit Devices/Deadbolts/Surface Mounted Closers/Butt Hinges/Continuous Hinges/Concealed Hinges/Viewers/Surface Mounted or Mortised Door Bottoms.

*See manufacturer’s installation instructions for additional information on Smoke and Draft Control, size restrictions, and limitations.
 
Configuration/Maximum Sizes
Single Swing 914.4mm wide by 2,438.4mm tall
(3’-0” wide by 8’-0” tall)
Standard Pair Not Allowed
Double Egress Not Allowed

Evaluated to the following:
Unless otherwise noted, the product listed above in this section has been evaluated for conformance to the following standards:
  • UL 10C – Positive Pressure Fire Test of Door Assemblies
  • NFPA 252 – Fire Test of Door Assemblies
  • CAN/ULC S104 – Standard Method for Fire Test of Door Assemblies
Listing Report Return to Search
Attributes
CriteriaCAN / ULC S104 (2015) (R2020)
CriteriaNFPA 252 (2017)
CriteriaUL 10(c) (2016) Ed. 3 (R:27 May 2021)
CSI Code08 10 00 Doors and Frames
Fire Resistance20 Min w/Hose Stream NP
Fire Resistance20 Min w/Hose Positive Pressure
Listing SectionCATEGORY A - DOORS - NO ADDITIONAL EDGE-SEALING SYSTEM REQUIRED