Product Description
90 Minute fire rated fire door and frame assembly (800F Series). 16 gauge steel or stainless steel faced, stiffened doors and 11 gauge steel or stainless steel frame assembly for installation in masonry wall (block adjacent to jambs must be fully grouted and a bond beam is required above the head of the frame) applications. The hinge jamb, lock jamb, and head of the frame must be fully grouted.
Configuration/Maximum Sizes |
Single Swing |
Overall Frame: 3’-4” wide by 8’-1 1/4” high
Opening Size 3’-0” wide by 7’-11 1/4” high |
Standard Pair |
Overall Frame: 6’-4” wide by 8’-1 1/4” high
Opening Size: 6’-0” wide by 7’-11 1/4” high |
Double Egress |
Not Allowed |
Door Thickness |
1 5/8” |
Minimum Jamb Depth |
6” |
Minimum Stop Height |
2” |
Limitations
Surface Vertical Rod (top and bottom latching)/Surface Mounted Closers/Vision Light Kit (maximum 100 in
2 clear view)/Louver (maximum 100 in
2 )/Mullion for Standard Pairs required (fully grouted)/3 Auxiliary Fire Pins required on the latch edge of door/4 Fire Bolts required on the hinge edge of the door (fire bolts are projected and engaged into the hinge jamb of the door frame when the door leaf is closed).
Evaluated to the following:
Unless otherwise noted, the product listed above in this section has been evaluated for conformance to the following test standards:
- UL 10C – Positive Pressure Fire Test of Door Assemblies
- NFPA 252 – Fire Test of Door Assemblies
- CAN/ULC S104 – Standard Method for Fire Test of Door Assemblies
This listing pertains to fire resistance only.