Intertek Directory of Building Products

Metl-Span ThermalSafe Fire Resistant Panels Company: Metl-Span, A Nucor Company Code Compliance Research Reports: CCRR-0553

PRODUCT COVERED
 
ThermalSafe™ Mineral Fiber Panels
 
PRODUCT DESCRIPTION
 
ThermalSafe panels are composite panel assemblies that sandwich a mineral fiber core between metal facers or “skins”.  Panels are not fully encapsulated by the metal skin—the mineral fiber core is exposed around all edges.
 
One edge has a square or “spline” groove cut into the mineral fiber core down the length of the panel.  The opposite edge of the panel has a square shape protrusion or “spline tongue” extending from the mineral fiber core running down the length of the panel.  This allows a tongue-and-groove fit of the mineral fiber cores between adjacent panels.  The main connecting mechanism between two panels is a tongue-and-groove connection made at the edge of the panels by the metal skins.  Panels are symmetric about their centerline with a nominal density of 8.5 pcf.
 
RATINGS

 
Panel
Thickness
Test Standard Design No. Rating
6 in. - ASTM E119
- UL 263
- CAN/ULC S101
MSN/CP 90-01 1.5 hours
6 in. - ASTM E119
- UL 263
- CAN/ULC S101
MSN/MWP 120-01 2 hours
8 in. - ASTM E119
- UL 263
- CAN/ULC S101
MSN/MWP 180-01 3 hours
4 in. - ASTM E119
- UL 263
- CAN/ULC S101
MSN/MWP 60-01 1 hour

Code Compliance Research Report (CCRR)
3", 4", 5", 6", 7" and 8" Panel thicknesses
Evaluation Method    Bulding Code CCRR NUmber
ICC-ES AC04
ICC-ES AC05
2021 International Building Code CCRR-0553
Listing Report Return to Search
Attributes
CriteriaCAN / ULC S101 (2014)
CriteriaICC-ES AC04 (2019)
CriteriaASTM E119 (2020)
CriteriaUL 263: 2011 Ed. 14 (R2020)
CSI Code07 41 63 Fabricated Roof Panel Assemblies
CSI Code07 42 13.19 Insulated Metal Wall Panels
Listing SectionWALL ASSEMBLIES
Listing SectionCEILING PANELS
Spec ID70355
Design Documents
Code Compliance Research Reports
Public Documents
No Results