20-minute (without hose stream) steel faced skin foam filled fire door. For use in any listed "Category C - Standard" Frame or in any listed "Category C - Proprietary" Frame in accordance with the frame manufacturer's individual listing(s) and installation instructions.
Field-Applied gasket is required (Category G gasket) on the header and sides of the frame (around the entire perimeter of the frame).
Limitations: Cylindrical locks and latches, deadbolts, surface mounted hardware, viewers, protection plates to 12" high.
Configuration |
Maximum Size |
Single |
3'-0" wide x 7'-0" high |
Evaluated to the following
Unless otherwise noted, the product listed above in this section has been evaluated for conformance to the following standards:
- UL 10C – Positive Pressure Fire Test of Door Assemblies
- NFPA 252 – Fire Test of Door Assemblies