Products Covered:
Smoke Guard Hose Stream 2100 Smoke & Fire curtain system.
Product Description:
The Smoke Guard Hose Stream 2100 system consists of two M2100 assemblies installed back-to-back. Each M2100 assembly is made of a filament glass fabric (identified as SGTex-30), which is wound onto a tube containing an internal drive system. Contained in a sheet metal housing, the curtain assembly is comprised of support rollers and associated electronics. The curtain edges are captured in vertical side guides during system deployment and the bottom edge of the curtain is attached to a weighted bottom bar. If the system encounters an alarm, the releasing device activates deploying the curtain. In the event of main power failure, an integrated battery system maintains the system. Should main and backup power systems fail, the curtain will deploy in a controlled manner under the influence of gravity (Gravity Fail Safe). If required, wall switches are provided on each side of the curtain, allowing occupants to momentarily raise the curtain to egress. After the alarm condition clears, the curtain automatically rewinds into the housing.
The Smoke Guard Hose Stream 2100 system, utilizing the SGTex-30 fabric, is recognized for use in fire-protection rated construction (as tested in accordance with UL10B, CAN/ULC S104, and NFPA 252), as described in the tables below.
FLAME SPREAD RATINGS
Test Standard |
Flame Spread |
Smoke Development |
ASTM E84 |
≤ 25 |
≤ 450 |
CAN/ULC S102 |
0 |
20 |
AIR LEAKAGE RATINGS
Test Standard |
Test Type |
Ratinga |
Size Restrictions |
UL 1784 |
Ambient & Elevated Temperatures |
≤3.0 cfm/ft2 at 0.10 in. of w.c. |
Min Area:19.5 ft2
Min Height: 3 ft |
≤3.0 cfm/ft2 at 0.30 in. of w.c. |
Min Area:42.25 ft2
Min Height: 5.5 ft |
aThis system was evaluated without an artificial bottom seal. The system may be installed in areas where pressurization is provided to control smoke movement in accordance with Section 4.3.2 of NFPA 105 (2019) and for hoistway opening protection and lobby doorways as allowed in Chapter 30 of the IBC.
FIRE-PROTECTION RATINGS
Test Standard
|
Test Type
|
Ratinga
|
UL 10B, NFPA 252, CAN/ULC S104
|
Fire Endurance
|
90 minutes with hose stream
|
aCurtains exceeding the tested dimensions of 10 ft x 10 ft must have an oversize label, issued by Intertek, stating the assembly is constructed in accordance with the certified design except for size. Acceptance of the oversize assembly is at the discretion of the Authority Having Jurisdiction.