Intertek Directory of Building Products

Karona 20 Minute (without hose stream) Stile and Rail MDF Fire Door Company: Karona, Inc.

FIRE RESISTANT PRODUCTS & COMPONENTS
Category “A” Doors – No Additional Edge-Sealing System Required
Category "A" Wood Core, swinging door for use in 20 minute positive pressure assemblies (also eligible for use in neutral pressure assemblies).  These doors are eligible for use in any "Category C - Standard Frames" when installed in masonry walls with the cavities of the frame fully grouted.  These doors may also be installed in frames listed in "Category C - Proprietary Frames" in accordance with the frame manufacturer's individual listing. 

Category “B” Doors – Additional Edge-Sealing System Required
Category "B" Wood Core, swinging door for use in 20 minute positive pressure assemblies (also eligible for use in neutral pressure assemblies).  A surface applied Category G intumescent edge seal system is required (minimum of 1" in width)These doors are eligible for use in any "Category C - Standard Frames".  These doors may also be installed in frames listed in "Category C - Proprietary Frames" in accordance with the frame manufacturer's individual listing.

Product Covered
Wood core type (stile and rail type), swinging door for installation in up to 20 minute (without hose stream) locations.

Limitations
Mortise or Cylindrical Latches with maximum 2-3/4" backset/VingCard Essence Mortise Card Lock/Surface Mounted Vertical Rod Fire Exit Devices/Rim Type Fire Exit Devices/Mortise Fire Exit Devices/Deadbolts/Surface Mounted Closers/Surface Mounted Protection Plates/Viewer/Surface Mounted Door Bottoms/Mortised Door Bottoms/EPT/Raceway/Reveals.
 
Configuration Maximum Size
Single Swing 3’-0” wide by 8’-0” high
Standard Pairs Not Allowed
Double Egress Not Allowed

Evaluated to the following...
This category includes doors evaluated without an edge-sealing system between the door and frame. It also includes doors evaluated with a sealing system incorporated (concealed or visible) into the edge of the door by the licensed manufacturer or machining distributor.

The door noted above is eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.
Listing Report Return to Search
Attributes
CriteriaUL 10(c) (2016) Ed. 3 (R:27 May 2021)
CriteriaNFPA 252 (2022)
CSI Code08 10 00 Doors and Frames
CSI Code08 14 00 Wood Doors
Fire Resistance20 Min w/out Hose Stream PP Cat A Door
Fire Resistance20 Min w/out Hose Stream PP Cat B Door
Listing SectionCATEGORY B - DOORS - ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
Listing SectionCATEGORY A - DOORS - NO ADDITIONAL EDGE-SEALING SYSTEM REQUIRED