Fire Resistant Products & Components
Category B Doors – Additional Edge Sealing System Required
Field applied gaskets (two strips of 1/2” wide or full width) are required (Category G) on the head of the door and the hinge and strike jamb of the frame or door (around the entire perimeter of the frame).
Product Covered
Brentwood Manufacturing 20 Minute Flush Wood Ballistic Fire Rated Door with Hose Stream.
Product Description
Hardware Limitations: Cylindrical / Cylindrical with Deadbolt / Mortise / Rim-Type Fire Exit Devices / Surface Mounted Fire Exit Devices / Surface Mounted Door Bottoms / Surface Mounted Closers / Surface Mounted Overhead Stops / Viewer / Protection Plates / Vision Kits (216 in
2).
Configuration |
Maximum Size |
Single Swing |
3’-0” wide by 7’-0” tall |
Standard Pair |
Not Allowed |
Double Egress |
Not Allowed |
The product noted above has been tested and qualified per UL 10C, NFPA 252, and CAN / ULC S104 for a 20 Minute Positive Pressure Fire Rating with Hose Stream.
These doors are eligible for use in any listed "Category C - Standard" hollow metal frame in accordance with the frame manufacturer's individual listing.
The door noted above is eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.