Intertek Directory of Building Products

Forte 20 Minute Flush Door (NP CAN/ULC S104) Company: Forte Opening Solutions

 
Wood Core Type (Particle Board, SCL, or Wood Stave), Swinging Flush Design Fire Door for installation in pairs in 20 minute locations (with Hose Stream.) For use in any "Category C - Standard" frame. These doors may also be installed in frames listed in "Category C - Proprietary" in accordance with the frame manufacturer's individual listing. 

Doors being used in neutral pressure applications (CAN/ULC S104 (2015) do not require the use of intumescent or gasket materials on the perimeter to meet fire endurance requirements. Gaskets may still be required to meet air leakage or smoke control requirements.
 
Limitations*
Mortise or Cylindrical Latches with maximum 5” backset/Card Locks**/Interconnecting Locks/Surface-Mounted Vertical Rod fire exit devices/Rim-Type fire exit devices/Concealed Vertical Rod exit devices/Deadbolts/Extension Flush Bolts with a maximum extension of 30 in./Pivot Hinges/Surface-Mounted Closers/Concealed Closer Arms/Surface Mounted or Concealed Overhead Stops/Floor Closers/Magnetic Switch/Viewer/Surface-Mounted or Mortised Door Bottoms/Electric Raceway/Vision Light Kit – Maximum 1296 sq./Power Transfer Units/Edge-Guards/Surface-Mounted Protection Plates/Applied Moulding/Reveals/Louver***
 
* See manufacturer’s installation instructions for additional information on Smoke and Draft Control, size restrictions, and limitations.

**See Machining Information section under locks and latches for additional approvals.

***When a louver is used the door assembly is not approved for smoke and draft applications.

Maximum Door Openings
Configuration Maximum Size Core
Single Swing 4’0” by 10’0” Particle Board or SCL
Standard Pair 8’0” by 9’0” SCL without top or bottom rail
Standard Pair 8’0” by 10’0” SCL with top and bottom rail*
Standard Pair 8’0” by 10’0” Particle Board
Double Egress 8’0” by 9’0” Particle Board or SCL
 
* The SCL core at 9'0" does not need a rail however at 10' top & bottom rails are required. 

Evaluated to the following...
This category includes doors evaluated with or without an edge-sealing system between the door and frame. 
 
Meeting edges of pairs may require an astragal or an edge-sealing system. Please refer to individual door listings.

These doors are eligible for use in any "Category C - Standard" frame. These doors may also be installed in frames listed in "Category C - Proprietary" in the accordance with the frame manufacturer's individual listing.

All doors listed  are eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.
 
All doors in this category are identified by a label or marking bearing the wording, "Listed Fire Door", a time interval, a temperature rise rating, a serial number and the Warnock Hersey Certification Mark and "CAN/ULC S104".
Listing Report Return to Search
Attributes
CriteriaCAN / ULC S104 (2015) (R2020)
CriteriaUL 10(b) (2008) (R2015)
CriteriaNFPA 252 (2017)
CSI Code08 10 00 Doors and Frames
CSI Code08 14 00 Wood Doors
Fire Resistance20 Min w/Hose Stream NP
Listing SectionDOORS
Spec ID74324
SwingSingle Swing
SwingStandard Pairs
SwingDouble Egress