FC-20 Category "A" Fire Rated Door Company: Forte Opening Solutions

FC-20 Fire Door with 20 Minute Proprietary Core. Flush or Panel type fire door for installation in single swing or pair of doors for 20 minute locations. For use in any Category "C" standard frame. 
Limitations
Cylindrical or mortise locks, minimum 1/2" bolt throw, cylindrical deadlock, mortised or surface applied automatic door bottoms, surface mount fire exit hardware, Concealed vertical rod fire exit hardware, wire raceway, surface mount or mortise flush bolts, surface mount or mortise closers, plant-ons, astragal optional, surface grooves on face (flush doors only).  Full radius top doors allowed.
Maximum Size of Openings
Singles  4'0" wide x 8'0" high
Pairs  7'0" wide x 8'0" high
Evaluated to the following...
Category A - Fire Doors (No additional Edge Sealing Required)
This category includes doors evaluated without an edge-sealing system between the door and frame. It also includes doors evaluated with a sealing system incorporated (concealed or visible) into the edge of the door by the licensed manufacturer or machining distributor.
Meeting edges of pairs may require an astragal or an edge-sealing system. Please refer to individual door listings.
These doors are eligible for use in any "Category C - Standard" frame. These doors may also be installed in frames listed in "Category C - Proprietary" in the accordance with the frame manufacturer's individual listing.
All doors listed in Category A are eligible to bear the "S" (for Smoke & Draft Control assemblies) if a listed "Category H - Smoke & Draft Control Gasket" has been applied to the assembly. Please refer to Category H for individual gasket manufacturer's listings.
All doors in this category are identified by a label or marking bearing the wording, "Listed Fire Door", a time interval, a temperature rise rating, a serial number and the Warnock Hersey Certification Mark and "UBC-7-2-97/UL 10C".
Listing Report Return to Search
Attributes
CriteriaUL 10(b) 2008 (R2009)
CriteriaUL 10(c) (2009)
CriteriaNFPA 252 (2012)
CriteriaUL 10(c) (2009) (R2015)
CriteriaCAN / ULC S104 (2015) (R2020)
CSI Code08 10 00 Doors and Frames
CSI Code08 14 00 Wood Doors
Fire Resistance20 Min w/Hose Stream PP Cat A Door
Listing SectionCATEGORY A - DOORS - NO ADDITIONAL EDGE-SEALING SYSTEM REQUIRED
Spec ID74332
SwingSingle Swing
SwingStandard Pairs
Design Documents
No Results
Public Documents
No Results