Intertek Directory of Building Products

Fantech, a Systemair Company - Ceiling Dampers for Use in Static Systems Company: Fantech, a Systemair Company

Product Covered:
Fantech, a Systemair Company - Ceiling Dampers for Use in Static Systems in Combination with Specified Fan Units (see table below):
 
Damper Type (Max. Size) Fantech Fan Model
484374
(11-1/4 in. x 12-1/4 in. x 3 in.)
SMPL80
SMPL100
SMPL80L
SMPL100L
SF50-80-100
SF50-80-100L
SFC50-80-100
SFC50-80-100H
SCF50-80-100HO
SCF50-80-100L
SCF50-80-100LH
SCG50-80-100LHO
484374 or 494046
(11-1/4 in. x 12-1/4 in. x 3 in.)
SC50-80-110
SC50-80-110L
S110-130-150
S110-130-150L
SC110-130-150H
SC110-130-150LH
SC110-130-150LHO

All fans listed above shall be Certified by Intertek to UL 507 to be eligible for use in combination with the UL 555C ceiling dampers.

All fans listed above shall be Certified by Intertek to CAN/CSA-C22.2 No. 113 to be eligible for use in combination with the CAN/ULC-S112.2 ceiling dampers.

Product Description:
The ceiling damper models in combination with an approved fan as listed in the table above are approved in accordance with UL 555C, as an alternative to a hinged-door sheet metal damper over a minimum 12 in. diameter duct outlet that has been previously approved in ASTM E119 or UL 263 fire resistance-rated floor/ceiling or roof/ceiling assemblies with a Restrained or Unrestrained Rating not to exceed 3 hours.  Maximum number of ceiling dampers and spacing shall be as specified in the design listing for the corresponding fire resistance-rated assembly.

The ceiling damper models in combination with an approved fan as listed in the table above are approved in accordance with CAN/ULC-S112.2, as an alternative to a hinged-door sheet metal damper over a minimum 12 in. diameter duct outlet that has been previously approved in CAN/ULC-S101 fire resistance-rated floor/ceiling or roof/ceiling assemblies with a Restrained or Unrestrained Rating not to exceed 3 hours.  Maximum number of ceiling dampers and spacing shall be as specified in the design listing for the corresponding fire resistance-rated assembly.

The ceiling damper and fan combination shall be installed in accordance with the manufacturer's installation instructions for either of the following two installation methods:
  1. Suspend the unit from the supporting construction with minimum 12 GA steel wire at each corner.
  2. Mount the unit by mechanically fastening the hanger bars to adjacent structural members excluding suspended ceiling support framing (ceiling grid). Four attachment points are required (one extending from each corner).  When fan unit is equipped with only three hanger bar attachment points, use the ceiling damper model (model 484374) equipped with four hanger bars.
Listing Report Return to Search
Attributes
CriteriaUL 555C (2014)
CriteriaCAN / ULC S112.2 (2007)
CSI Code23 33 00 Air Duct Accessories
Listing SectionDAMPERS
Spec ID74526
Design Documents
No Results
Public Documents