MPI KY, LLC - 20-90 Min Temp Rise Steel Stiffened Fire Doors
Company: MPI KY LLC
FIRE DOORS - NEUTRAL PRESSURE
Steel Stiffened Temperature Rise Fire Doors for installation Singly or Pairs, in 20 minute up to and including 90 minute locations.
Size Limitations
Single Swing 4'0" wide x 9'0" high
Standard Pairs 8'0" wide x 9'0" high (4'0" each leaf)
Limitations*
Mortise or Cylindrical Latches with maximum 5" Backset/Fire Exit Devices/Listed Mortised, Manual or Automatic Flush Bolts/Viewer/Vision Panels. Temperature Rise is 450°F at 30 Minutes.
Evaluated to the following...
Unless otherwise noted, assemblies in this section have been evaluated for conformance to the following standards:
ASTM-E152, Methods of Fire Tests of Door Assemblies
CSFM-43.7, Methods of Fire Tests of Door Assemblies
CAN4-S104(ULC-S104), Standard Method for Fire Tests of Door Assemblies
NFPA-252, Standard Methods for Fire Tests of Door Assemblies
UBC-7-2-94, Uniform Building Code
UL-10(b), Fire Tests of Door Assemblies
and are installed in accordance with the following:
NFPA-80, Fire Doors and Windows
Manufacturer's Instructions.
All assemblies are identified by a label or marking bearing the wording, "Listed (Product)", a time interval, temperature rise (if applicable), a serial number and the WHI Certification Mark.
(Unless otherwise specified, all Fire Doors have a nominal thickness of 1-3/4".)