McKEON FE6000 Forced Entry Resistant Door
FORCED ENTRY RESISTANCE RATING
| Test Standard |
Maximum Sizea |
Rating |
| ASTM F3038 |
30'-0" wide
22'-0" high |
60 Minutes |
aWidth is tip to tip of support guide angles
BULLET RESISTANCE RATING
| Test Standard |
Rating |
| UL 752 (11th Edition) |
Level 1 |
INSTALLATION LIMITATIONS
Assemblies must be installed on the protected (non-attack) face of the supporting wall.
When mounted to steel supporting structure, Mounting Angles are anchored with minimum 5/8" diameter A325 bolts spaced maximum 12 inches on-center. Structural adequacy of steel supporting structure is to be determined by others and is not evaluated as part of this Listing.
When mounted to concrete supporting structure, Mounting Angles are anchored with 5/8" diameter Simpson Strong-Bolt 2 wedge anchors spaced maximum 12 inches on-center. The tested condition utilized 4000-psi strength concrete, an embedment length of 5-1/8 inches and an edge distance to the opening of 7-1/2 inches. Adequacy of concrete supporting structure is to be determined by others and is not evaluated as part of this Listing.
Alternate anchoring to supporting structure that maintains the maximum spacing of 12 inches on-center is to be designed by a registered design professional.
Installation shall follow these listing procedures and the manufacturer's instructions provided with each assembly. In the event of a conflict, these listing procedures govern.