U.S. Smoke & Fire Corp - SD240GS Fire Protective Smoke Curtain Company: U.S. Smoke & Fire Corp

Products Covered:
U.S. Smoke & Fire Corp Model SD240GS Fire Protective Smoke Curtain tested in accordance with UL 1784, and with UL 10D for a 90 minute rating.

Product Description:
The U.S. Smoke & Fire Corp Model SD240GS fire protective smoke curtain consists of a filament glass fabric, which is wound onto a tube containing an internal drive system. The configurations can either be single or multi-roller. Contained in a sheet metal housing, the curtain assembly is comprised of support rollers and associated electronics. The curtain edges are captured in vertical side guides during system deployment and the bottom edge of the curtain is attached to a weighted bottom bar. If the system encounters an alarm, the releasing device activates deploying the curtain.  Should main and backup power systems fail, the curtain will deploy in a controlled manner under the influence of gravity (Gravity Fail Safe). If required, wall switches are provided on each side of the curtain, allowing occupants to momentarily raise the curtain to egress. 

Maximum Size (single roller)a (see Fire Ratings Table below)
Drop Height 46'0"
Opening Width 25'0"

Maximum Size (multiple roller)a (see Fire Ratings Table below)
Drop Height 46'0"
Opening Width 120'0"

Minimum Size **
Drop Height 6'6"
Opening Width 7'0"
**(size tested)

Curtain Overlap:  Minimum fabric overlap with multiple roller assemblies 24" 
Minimum bottom bar weight: 7.4 lb/ft 
Minimum side guide anchorage: 3/8" by 6" long self-drilling screws 12" o.c.
Minimum headbox anchorage:  #14 by 2-1/2" long self drilling screws 16" o.c.

FIRE RATINGS 
Test Standard Test Type Ratinga,b
UL 10D Fire Resistance                         90 Minutes                     
UL 10B, UL 10C, and NFPA 252
Fire Endurance
20 minutes without hose stream
aCurtains exceeding the tested dimensions of 10 ft x 10 ft must have an oversize label, issued by Intertek, stating the assembly is constructed in accordance with the certified design except for size. Acceptance of the oversize assembly is at the discretion of the Authority Having Jurisdiction.
bThe UL 10B, UL 10C, and NFPA 252 standards apply to 20 Minute Fire Endurance ratings without hose stream only.  Acceptance of the UL 10B, UL10C, and NFPA 252 ratings for the fire curtain product noted above is ultimately at the discretion of the Authority Having Jurisdiction.

AIR LEAKAGE RATINGS 
Test Standard Test Type Ratinga
UL 1784 Ambient Temperature ≤3.0 cfm/ft2 at up to 0.10 in. of w.c.
UL 1784 Elevated Temperature ≤3.0 cfm/ft2 at up to 0.10 in. of w.c.
aThis assembly was tested without an artificial bottom seal. The assembly may be installed in areas where pressurization is provided to control smoke movement in accordance with Section 4.3.2 of NFPA 105 (2019) and for hoistway opening protection and lobby doorways as allowed in Chapter 30 of the 2018 IBC.
 
Listing Report Certificate of Compliance Return to Search
Attributes
Certificate Date of ExpiryDecember 31, 2026
Certificate Date of Initial RegistrationAugust 16, 2024
Certificate NumberWHI24-32826703
CriteriaUL 1784 (2015)
CriteriaUL 10(c) (2009) (R2015)
CriteriaUL 10(d) (2014)
CriteriaUL 10(b) (2008) (R2015)
CriteriaNFPA 252 (2017)
CSI Code08 30 00 Specialty Doors and Frames
CSI Code08 34 00 Special Function Doors
Listing SectionCATEGORY I - SMOKE & DRAFT CONTROL DOOR ASSEMBLIES
Spec ID80188